Product Center

+
  • 9(540).jpg

PYF SDc-K smoke exhaust valve (plate type smoke exhaust port)

  • Commodity name: PYF SDc-K smoke exhaust valve (plate type smoke exhaust port)

Phone:

  • Product Description
  • Technical parameters
  • Performance

    1、 Normally closed, when a fire occurs, the smoke sensor sends an electrical signal ( DC24V) to the control center, the electromagnet in the actuator is energized, the valve opens automatically, and outputs an opening electrical signal.

    2、 The valve can be opened manually.

    3、  Manual reset after valve operation.

     

    Structure

    Main components: valve body, blade, shaft, bushing, actuator, etc.

    Maximum valve size: 800*800

    Matching actuator model: JPYF SDc-K-b

    W×H matching duct size

     

    Conditions of use

    Static       Pressure: Below 1500Pa

    Maximum air flow rate: 15 m/s

    Ambient operating temperature: -10℃~50℃

    Ambient operating humidity: Relative humidity Below 85%

  •  

    Main Technical Parameters

    Air Leakage (Pressure Difference 1000Pa) ≤700m3/m2.h

    Control Voltage: DC24V

    Operating Current: ≤0.7A

    Microswitch Contact Capacity: AC220V 3A

    Operating Time: Instantaneous

     

    Circuit Diagram

       Red wire : DC24V “+” pole

    Blue wire : DC24V “-” pole

    Yellow wire : Signal line

     

    Precautions

    1. Users should not paint the outside of the actuator during use, and should not add oil to the electrical components, as this may cause malfunctions.

    2. Fire dampers are related to life safety and must be installed and debugged by professionals. Regular checks of opening, closing, electrical signal operation, and temperature sensors should be performed every six months during normal use.

Keywords:

Product Inquiry

Please leave your email address, and our professionals will contact you as soon as possible!