Product Center

+
  • 11(548).jpg

PYF SDc-YK smoke exhaust valve (plate type smoke exhaust port)

  • Commodity name: PYF SDc-YK smoke exhaust valve (plate type smoke exhaust port)

Phone:

  • Product Description
  • Technical parameters
  • Performance

    1、 Normally closed, in case of fire, the smoke sensor sends an electrical signal ( DC24V) to the control center, energizing the electromagnet in the actuator, automatically opening the valve and outputting an opening electrical signal.

    2、 The valve can be opened manually.

    3、  After the valve operates, it can be reset remotely via a steel wire rope.

     

    Structure

    Main components: valve body, blade, shaft, bushing, actuator, etc.

    Maximum valve size: 800*800

     

    Matching actuator model: KPY SDc-KY

    W×H matching duct size

     

    Conditions of use

    Static       Pressure: Below 1500Pa

    Maximum air velocity: 15 m/s

    Ambient operating temperature: -10℃~50℃

    Ambient operating humidity: Relative humidity Below 85%

  • Main Technical Parameters

    Air Leakage (Pressure Difference 1000Pa) ≤700m3/m2.h

    Control Voltage: DC24V

    Operating Current: ≤0.7A

    Microswitch Contact Capacity: AC220V 3A

    Operating Time: Instantaneous

     

    Circuit Diagram

     

    Precautions

    1. Users should not paint the outside of the actuator during use, and should not add oil to the electrical components, as this may cause malfunctions.

    2. Fire dampers are critical for life safety and must be installed and commissioned by professionals. Regular checks of the opening, closing, electrical signal operation, and temperature sensor should be performed every six months during normal use.

Keywords:

Product Inquiry

Please leave your email address, and our professionals will contact you as soon as possible!