PYF SDj-YK smoke exhaust valve
- Commodity name: PYF SDj-YK smoke exhaust valve
- Product Description
- Technical parameters
-

Performance :
1、 Normally open, in case of fire, the smoke (temperature) sensor sends an electrical signal ( DC24V) to the control center, the motor in the actuator is energized, the valve automatically closes, and outputs a closed electrical signal.
2、 The DC motor drives the reset after the valve action.
3、 The valve can be manually closed and manually reset.
4、 Action signals or reset signals are fed back to the control center and the starting interlock device.
Structure :
Main components: valve body, blade, shaft, bushing, temperature sensor, actuator, stainless steel spring plate, torsion spring, etc.
Matching actuator model: JPYF SDj-YK
Maximum valve size: 1250*800
W×H matches the duct size, and the flange size is the same as the flange of the metal rectangular duct in national standard GB50234-2002.
Conditions of use :
Static Pressure: Below 1500Pa
Maximum air velocity: 15 m/s
Ambient temperature: -10℃~50℃
Ambient humidity: Relative humidity Below 85%
-
Main Technical Parameters :
Air Leakage (Pressure Difference 1000Pa) ≤700m3/m2.h
Control Voltage: DC24V
Operating Current: ≤0.7A
Reset Current: ≤0.7A
Rotation Direction: Counterclockwise opening during operation
Reset Time: ≤12 seconds
Microswitch Contact Capacity: AC220V 3A
Operating Time: Instantaneous
Circuit Diagram :

Line 1: DC24V “+” level
Line 3: DC24V “+” level
Line 5: Signal line
Line 6: DC24V “-” level

Precautions
1. Users should not paint the outside of the actuator or add oil to the electrical components during use, as this may cause malfunctions.
2. Fire dampers are critical for life safety and must be installed and commissioned by professionals. Regular checks of opening, closing, electrical signal operation, and temperature sensors should be performed every six months during normal use.