Product Center

+
  • ZCP.jpg

ZCP temperature control disc diffuser

Installed on the ceiling, it automatically detects the blowing temperature during cooling and heating, and the center plate can move up and down to automatically adjust the airflow direction. During summer cooling, it blows horizontally. During winter heating, it blows vertically. It has a small amount of induced air, and the blown air is not easily slowed down, so it can reach a longer blowing distance. A temperature-sensing sensor is used, and no electricity is used. Cooling temperature is below 17°C, and heating temperature is above 28°C. After the temperature sensor is activated, it is in the cooling or heating state. The outer frame and blades are assembled, and there are no welding points.
  • Commodity name: ZCP temperature control disc diffuser

Phone:

  • Product Description
  • Technical parameters
  •  

    Size Chart:

    ZCP Size Chart of Temperature Control Disc Diffuser

    φC (Neck Size)

    φA (Face Size)

    φB (Aperture Size)

    H

    E

    T

    N

    φ150

    φ340

    φ290

    125

    80

    15

    35

    φ200

    φ440

    φ380

    135

    80

    20

    40

    φ250

    φ520

    φ460

    145

    80

    20

    40

    φ300

    φ610

    φ550

    155

    80

    25

    45

    φ350

    φ710

    φ630

    165

    80

    25

    50

     

     

     

     

  •  

    ZCP Performance Table of Temperature Control Disc Diffuser

     

    Neck Size

    Air          Speed m/s

    2.0

    2.5

    3.0

    3.5

    4.0

    4.5

    5.0

    6.0

     

    Air          Volume m 3/h

    131

    163

    196

    228

    261

    294

    326

    392

     

    Static Pressure Loss pa

    H

    9

    14

    19

    26

    35

    44

    54

    78

     

    V

    10

    16

    23

    31

    41

    51

    64

    91

    φ 150

    Diffusion Radius m

    H

    0.5

    0.6

    0.7

    1.8

    1.0

    1.1

    1.2

    1.4

     

    Reach Distance m

    V

    2.2

    2.8

    3.3

    3.9

    4.4

    5.0

    5.5

    6.6

     

    Noise Generation dB(A)

    H

    ~

    ~

    25

    29

    33

    36

    39

    45

     

    V

    ~

    ~

    25

    30

    34

    38

    41

    46

     

    Air          Volume m 3/h

    231

    288

    346

    403

    461

    519

    576

    692

     

    Static Pressure Loss pa

    H

    9

    14

    19

    26

    35

    44

    54

    78

     

    V

    10

    16

    23

    31

    41

    51

    64

    91

    φ 200

    Diffusion Radius m

    H

    0.7

    0.9

    1.0

    1.2

    1.4

    1.6

    1.7

    2.1

     

    Reach Distance m

    V

    3.2

    4.0

    4.8

    5.6

    6.4

    7.2

    8.0

    9.6

     

    Noise Generation dB(A)

    H

    ~

    ~

    26

    30

    34

    37

    40

    46

     

    V

    ~

    21

    26

    31

    35

    38

    41

    47

     

    Air          Volume m 3/h

    359

    448

    538

    628

    718

    807

    897

    1076

     

    Static Pressure Loss pa

    H

    9

    14

    19

    26

    35

    44

    54

    78

     

    V

    10

    16

    23

    31

    41

    51

    64

    91

    φ 250

    Diffusion Radius m

    H

    0.9

    1.1

    1.3

    1.5

    1.7

    1.9

    2.1

    2.6

     

    Reach Distance m

    V

    4.1

    5.1

    6.2

    7.2

    8.2

    9.2

    10.3

    12.3

     

    Noise Generation dB(A)

    H

    ~

    21

    26

    31

    35

    39

    42

    47

     

    V

    ~

    23

    28

    33

    36

    40

    43

    48

     

    Air          Volume m 3/h

    515

    644

    773

    902

    1031

    1159

    1288

    1546

     

    Static Pressure Loss pa

    H

    9

    14

    19

    26

    35

    44

    54

    78

     

    V

    10

    16

    23

    31

    41

    51

    64

    91

    φ 300

    Diffusion Radius m

    H

    1.0

    1.2

    1.4

    1.7

    1.9

    2.1

    2.4

    2.9

     

    Reach Distance m

    V

    5.3

    6.6

    7.9

    9.3

    10.6

    11.9

    13.2

    15.9

     

    Noise Generation dB(A)

    H

    ~

    22

    27

    32

    36

    40

    43

    48

     

    V

    ~

    24

    29

    34

    38

    41

    44

    49

     

    Air          Volume m 3/h

    700

    875

    1050

    1225

    1400

    1575

    1750

    2100

     

    Static Pressure Loss pa

    H

    9

    14

    19

    26

    35

    44

    54

    78

     

    V

    10

    16

    23

    31

    41

    51

    64

    91

    φ 350

    Diffusion Radius m

    H

    1.1

    1.3

    1.6

    1.9

    2.1

    2.4

    2.7

    3.2

     

    Reach Distance m

    V

    5.8

    7.2

    8.7

    10.1

    11.5

    13.0

    14.4

    17.3

     

    Noise Generation dB(A)

    H

    ~

    23

    28

    33

    37

    41

    44

    50

     

    V

    ~

    25

    30

    35

    39

    42

    45

    50

    H For horizontal blowing, V For vertical blowing.

               

    ■Reach distance is the air speed 0.5m/s at the location.

               

    ■When the noise generation is below 20dB(A), it is represented by [~].

               

                                                                                       

Keywords:

Product Inquiry

Please leave your email address, and our professionals will contact you as soon as possible!