Product Center

+
  • GLLV条缝型散流器.jpg

GLLV Slit type diffuser

GLLV Slit type diffuser are generally installed on ceilings, but can also be installed on side walls or other locations.
  • Commodity name: GLLV Slit type diffuser

Phone:

  • Product Description
  • Technical parameters
  •  

    Made of aluminum profiles, the surface is anodized, and can also be anodized, electrostatically sprayed, or baked according to decorative requirements. 
    It can be used for both supply and return air. Each slot has two adjustable blades to control airflow direction and volume, which can be easily adjusted from the outside. 
    The blades are generally black. 
    Can be used with a plenum chamber. 
    The maximum length of a single piece is 3 meters, and longer lengths can be spliced together.

  • GLLV Performance Table of Slot Diffusers

    Type

    Air Discharge Velocity m/s

    1.0

    2.0

    3.0

    4.0

    5.0

    6.0

    7.0

    8.0

    1 S

    Air Volume CMH

    70

    140

    211

    281

    351

    421

    491

    562

    Static Pressure Loss pa

    H

    1

    3

    6

    11

    17

    23

    32

    42

    V

    <1

    1

    3

    6

    8

    13

    18

    23

    Reach Distance m

    H

    0.6

    1.3

    2.0

    2.7

    3.4

    4.1

    4.8

    5.4

    V

    0.6

    1.3

    2.1

    2.8

    3.5

    4.2

    5.0

    5.7

    Noise dB(A)

    H

    ~

    ~

    ~

    25

    31

    36

    40

    43

    V

    ~

    ~

    23

    30

    35

    39

    43

    46

    2 S

    Air Volume CMH

    140

    281

    421

    562

    702

    842

    983

    1123

    Static Pressure Loss pa

    H

    1

    5

    12

    21

    33

    48

    65

    84

    V

    1

    3

    7

    13

    20

    28

    39

    51

    Reach Distance m

    H

    1.4

    2.8

    4.3

    5.8

    7.3

    8.7

    10.2

    11.7

    V

    1.2

    2.6

    3.9

    5.2

    6.6

    7.9

    9.3

    10.6

    Noise dB(A)

    H

    ~

    ~

    23

    30

    36

    41

    45

    48

    V

    ~

    ~

    ~

    29

    36

    42

    46

    52

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     H indicates horizontal discharge, V indicates vertical discharge. The reach distance refers to the distance from the outlet to the point where the air velocity is 0.5m/sec.

     The reach distance needs to be corrected due to the length of the outlet and the temperature difference of the discharged air.

Keywords:

Product Inquiry

Please leave your email address, and our professionals will contact you as soon as possible!